Dynamic Performance Analysis of a Distribution Feeder With a Transportable Storage System Connected

Souza Neto, Lucas Hack de, Naspolini, Helena Flávia, Aquino, Antônio Felipe da Cunha, Hirassaki, Vinícius, Abreu, João Pedro Frederico, Dall’Asta, Angélica Paula Caús, Bortoluzzi, Gabriel Wolf, Pacheco, Leonardo Freire, Rüther, Ricardo

ISES Solar World Congress 2025 · Fortaleza, Brazil · 2025-11-03
Published by International Solar Energy Society (ISES)
DOI: 10.18086/swc.2025.03.22

Abstract

The study analyzes the effects of integrating a Transportable Battery Energy Storage Systems (TBESS) into a distribution feeder under both steady-state and transient conditions, evaluating its performance in load supply, reactive power supply and power quality within a feeder. The performance analysis focuses on electrical quantities at nodes along a 13.8 kV feeder, calculated through EMT simulations that consider a detailed representation of both the electrical network and the TBESS. The study examines steady-state conditions and the occurrence of a three-phase short-circuit, both with and without the TBESS in operation. In addition to the benefits related to load supply, the TBESS is found to provide a slight improvement in voltage levels regardless of whether operated in voltage profile support mode or load supply. The results indicate that the steady-state and transient demands observed are compatible with the grid requirements, suggesting that the TBESS can be considered a viable solution to support the continuity and quality of power supply in various operational and emergency scenarios.

Keywords

TBESS, Distribution Network, On-Grid, EMT simulations